IN-WALL FLUSH MOUNT FUEL TRANSFER FILL BOX
|
|
Phillips Pump offers fuel oil fill boxes to contain oil spills specifically for those
instances where an inside tank is filled from the outside.
When used in conjunction with a flush mounted through the wall hook-up, this solution protects
fuel supply lines from damage, vandalism or unauthorized access.
Since our fill boxes can be easily accessed, they allow for tank refilling without infringing upon
property lines, or where there is limited filling space.
Our FCPM and FCSPM series in-wall, flush mount fill boxes are integrated engineered packaged
systems with controls for filling operations. With a high level indicator and monitoring
built into the box, controls include leak detection circuitry that prevents the filling of leaking tanks,
operator warnings at the 90% tank full level and lock out of all filling operations when the tank
is full. Visual and audible alarms and indicator lights are also provided.
Should a spill occur, the five gallon containment sump provides protection and a 1/2" NPT
drain port allows easy removal of any escaped oil.
Multi-tank applications are also possible. Please contact us to discuss your specific
design. As with all Phillips Pump fuel transfer products, our in-wall fill boxes
are fully compatible with, and can communicate with, our pump sets and
day tanks, to bring you
a single design source for all your fuel transfer equipment needs.
Each Phillips Pump In-Wall System Includes:
- NEMA 4 rated enclosure
- 5 gallon containment sump with 1/2" NPT drain port
- Fully gasketed door with chrome plated locking door handle
- Available in 14 gauge carbon steel with durable rust-resistant outer finish or 304 stainless steel
- Dry break disconnect and dust cover
- Net Weight: 135 lbs
- Designed to meet the specific requirements of each application,
special dimensions and a wide range of
system options are available
- Our carbon steel (FPM series) and stainless
steel (FSPM series) are stand alone fill boxes
- Our FCPM series and FCSPM
series
include an overfill prevention controller with:
- Tank full / tank high level, and leak detected visual alarms
- Audible alarm buzzer
- Power on indicator light
- System open/close and system reset push-buttons
- Interface with existing third party tank gauging systems or
bi-level float switch for tank full and tank high level warnings are available
- Optional solenoids are available for installation in the fuel supply lines
to lock out filling operations at tank full and tank high alarm levels
- 115 VAC, 60 Hertz required, other voltages are available upon request
- Our FCPM-DR series and our FCSPM-DR
series
include a digital tank level readout with the alarms listed above
- The DR series interfaces with optional level probes listed below or with existing
third party tank gauging systems having a 4 - 20 mA output
(note: 115 VAC required, other voltages are available)
|
Model No. |
Application |
Material |
Product Code
|
FPM |
Fill Box only |
Carbon Steel |
1106 |
FSPM |
Fill Box only |
304 SS |
1271 |
FCPM |
Carbon steel fill box with overfill controls |
Carbon Steel |
3482 |
FCSPM |
Stainless steel fill box overfill controls |
304 SS |
3647 |
FCPM-DR |
Carbon steel fill box with overfill controls and tank level LCD display |
Carbon Steel |
3962 |
FCSPM-DR |
Stainless steel fill box overfill controls and tank level LCD display |
Stainless Steel |
4130 |
Basic Dimensions |
|
Our Most Popular Options |
Option |
|
Description |
Product Code |
1030 |
a |
Dry type disconnect, aluminum body, viton seals with dust cover, 1 1/2"
(note: shipped loose,
location determined by installer)
|
197 |
|
b |
Dry type disconnect, aluminum body, viton seals with dust cover,
2" (note: shipped loose,
location determined by installer)
|
231 |
1080 |
c |
Dry type disconnect, aluminum body, viton seals with dust cover,
2" (note: shipped loose,
location determined by customer)
|
445 |
|
f |
Solenoid valve, bronze, 120 VAC, normally closed, 2" NPT (note: shipped loose for
installation in fuel supply line)
|
895 |
|
g |
Solenoid valve, bronze, 120 VAC, normally closed, 3" NPT (note: shipped loose for
installation in fuel supply line)
|
895 |
1191 |
a |
Float type piping leak detection sensor with 1/2" NPT fitting |
174 |
|
b |
Encased float type tank interstitial leak detection sensor,
2" NPT tank top mounting |
382 |
1250 |
a |
Auxiliary high level float switch for tank high level alarm (note:
1" NPT
tank top fitting required)
|
207 |
|
b |
Bi-level float switch for tank full and tank high level alarms
(note: 2" NPT tank top fitting required)
|
343 |
1252 |
|
Pressure type level gauge, 4-20 mA output (to be used with type DR models) with junction
box (note: 2" NPT tank top fitting required)
|
1759 |
| |
|