IN WALL FLUSH MOUNT CARBON STEEL FILL STATION
A.
Fuel oil supply main storage fill lines shall terminate at the building
wall in a Phillips Pump Part Number FPM in-wall flush mount fill box. The fill box
shall be of NEMA 4 construction, have a spill containment basin with a minimum of
5
U.S. gallon holding capacity, a gasketed door with three point latching mechanism
and chrome plated locking handle and be equipped with 1/2" NPT drain connection.
The fill box shall be equipped with flanges mounted to assure that cabinet
face is flush with mounting surface, shall be of 14 gauge carbon steel construction
with external chemical resistant gray enamel finish over rust-resistant primer. Fill box
to be manufactured by Phillips Pump LLC Bridgeport, CT or equal.
B.
Fuel oil supply fill box enclosure shall come with __ " size oil fill
connection dry break type disconnect aluminum body with viton seals and dust cover.
|