Single And Double Wall Day Tanks
|
Phillips Pump single wall (PDT) and double wall (PDWT) series day tanks provide a ready supply of oil
or diesel fuel for boilers, diesel generators, or other stationary, engine-driven or burner-fired
equipment. With capacities ranging from 25 to 500 gallons, Phillips Pump
day tanks may be selected
for maximum fuel capacity for placement in a minimum amount of space.
All tanks are manufactured in accordance with a UL 142 label and meet NFPA 30 standards. Each Phillips
Pump day tank is constructed from 10 gauge steel, internally reinforced and seam welded to provide long lasting
life in rugged industrial and commercial environments.
Each tank is pressure tested with a 5 PSI rating, and has an internal epoxy coating with an external
chemical-resistant enamel finish over a rust-resistant primer.
Single Wall PDT Series
Our PDT series single wall day tank includes a mechanical gauge as a visual level indicator, a UL sized vent
port, a 4 1/2" diameter inspection / emergency vent port, 2" NPT manual fill port,
1" NPT pump-fill
engine supply, an engine return and overflow, and drain ports
(fitting schedule).
Each Phillips Pump Single Wall Day Tank Includes:
- Heavy gauge, seam welded, reinforced steel tank with heavy gauge steel channel support base with
mounting holes
- Mechanical tank gauge for visual level indication
- Corrosion-resistant internal epoxy coated
- Complete array of fittings and connections
- Engine supply and pump supply ports with supplied with drop tubes
- 150% and 200% optional rupture containment basins are available
- Other Phillips Pump day tank
options are available
to meet the specific requirements for each application
|
|
Day Tank
| Optional 150% Containment Rupture Basin
|
Style |
Gallons |
Model No. |
Tank Dimensions W" x D" x H" |
Style |
Model No. |
Tank Dimensions w/ Rupture Basin W" x D" x H" |
Single Wall |
25 |
PDT-25 |
24"x 24"x 16" |
Rupture Basin |
PRB-25 |
34"x 32"x 19" |
|
50 |
PDT-50 |
24"x 24"x 26" |
|
PRB-50 |
34"x 32"x 29" |
|
60 |
PDT-60 |
24"x 24"x 29" |
|
PRB-60 |
34"x 32"x 32" |
|
75 |
PDT-75 |
24"x 24"x 35" |
|
PRB-75 |
34"x 32"x 38" |
|
100 |
PDT-100 |
24"x 24"x 45" |
|
PRB-100 |
34"x 32"x 48" |
|
150 |
PDT-150 |
36"x 36"x 32" |
|
PRB-150 |
46"x 44"x 35" |
|
200 |
PDT-200 |
36"x 36"x 41" |
|
PRB-200 |
48"x 44"x 44" |
|
250 |
PDT-250 |
36"x 36"x 50" |
|
PRB-250 |
48"x 44"x 53" |
|
275 |
PDT-275 |
36"x 36"x 54" |
|
PRB-275 |
48"x 44"x 57" |
|
325 |
PDT-325 |
48"x 36"x 48" |
|
PRB-325 |
60"x 48"x 51" |
|
400 |
PDT-400 |
48"x 48"x 45" |
|
PRB-400 |
60"x 60"x 48" |
|
500 |
PDT-500 |
48"x 48"x 55" |
|
PRB-500 |
60"x 60"x 58" |
|
|
* Note: 200% and other size containment basins are also available. Please
contact us for additional information.
Double Wall PDWT Series
The Phillips Pump PDWT series double wall day tanks come complete with a higher capacity outer chamber
to protect against spills or leaks due to a high pressure rupture of, or internal damage to, the inner
day tank.
Each day tank includes a mechanical gauge as a visual level indicator, a primary tank
UL sized vent port and 4" NPT inspection / emergency vent port, a secondary containment emergency vent
port, 2" NPT manual fill port, a rupture basin leak switch port, 1" NPT pump-fill
engine supply, an engine return and overflow, and drain ports
(fitting schedule).
Each Phillips Pump Double Wall Day Tank Includes:
- Heavy gauge, seam welded, reinforced steel tank with heavy gauge steel channel support base with
mounting holes
- Mechanical tank gauge for visual level indication
- Corrosion-resistant internal epoxy coated
- Complete array of fittings and connections
- Engine supply and pump supply ports with supplied with drop tubes
- Standard 135% containment outer chamber
- Tank options are available
to meet the specific requirements for each application
Style |
Gallons |
Model No. |
Dimensions H" x D" x W" |
Double Wall |
25 |
PDWT-25 |
34"x 32"x 19" |
|
50 |
PDWT-50 |
34"x 32"x 29" |
|
60 |
PDWT-60 |
34"x 32"x 32" |
|
75 |
PDWT-75 |
34"x 32"x 38" |
|
100 |
PDWT-100 |
34"x 32"x 48" |
|
150 |
PDWT-150 |
46"x 44"x 35" |
|
200 |
PDWT-200 |
48"x 44"x 44" |
|
250 |
PDWT-250 |
48"x 44"x 53" |
|
275 |
PDWT-275 |
48"x 44"x 57" |
|
325 |
PDWT-325 |
60"x 48"x 51" |
|
400 |
PDWT-400 |
60"x 60"x 48" |
|
500 |
PDWT-500 |
60"x 60"x 58" |
|
|
* Note: 200% and other size containment basins are also available. Please
contact us for additional information.
|
|
Our Most Popular Options
Option |
Description |
1010 |
Auxiliary hand pump, rotary vane type, 10 GPM at 135 RPM |
1015 |
Auxiliary hand pump, piston type, 20 GPM per 100 strokes |
1025 |
Manual fuel fill cap, 2" lockable |
1040 |
Wall mounting brackets (available on double wall tanks or single wall tanks without basin) |
1050 |
Pipe stand adapters to raise tank above floor |
1063 |
Vent cap, screened, for installation at outdoor vent termination |
1064 |
Emergency vent, 4" NPT |
1065 |
Drain valve with locking handle |
1080 |
Solenoid valve, normally closed to prevent loss of prime or tank flooding |
1081 |
Solenoid valve, normally open, to shut down flow for additional protection in case of a high level alarm |
1082 |
Flow control manifolds, factory assembled units consisting of: i) one normally closed solenoid valve to
direct flow for multi-tank applications and to prevent loss of prime or tank flooding, ii) one normally
open solenoid valve to shut down flow and provide additional protection in case of a high level tank
condition, and iii) two isolation valves and manual bypass tee with ball valve
|
1087 |
Manual shut off ball valves, bronze body |
1088 |
Manual shut off ball valves, fire rated |
1090 |
Foot valve, 1" NPT on engine supply drop tube to prevent loss of prime |
1130 |
Extra engine supply or engine return pipe connections; includes drop tubes
(please specify location and quantity)
|
1132 |
Extra piping connections (please specify location and quantity) |
1135 |
Oversized piping connections |
1191 |
Rupture basin leak sensor (available for double wall tanks or single wall tanks with basin) |
1197 |
Fuel in vent detection sensor |
1211 |
Sight glass with steel guard and valves |
1250 |
Single level float level probe, Buna N float with brass stem and locking rings, single
level (note: typically for high level auxiliary indication)
|
1251 |
Dual level float level probe, Buna N float (note: typically for high and low level
auxiliary indication, or pump on and pump off signals)
|
1252 |
Float level probe, Buna N float, 3 level (note: typically for high level
auxiliary indication, with pump on and pump off signals)
|
1253 |
Float level probe, Buna N float, 4 level (note: typically for high and low level
alarm indication, with pump on and pump off signals)
|
1254 |
Float level probe, Buna N float, 5 level (note: typically for high-high, high and low level
alarm indication, with pump on and pump off signals)
|
|
| |
|